Best Applications for Water Shedding Standing Seam Metal Roof Panels

A standing seam roof system, or SSRS, has exposed fasteners only at the eave and at specially designed end laps. The concealed clips installed at the panel seam typically allow the panel to float during thermal movement. These systems are normally manufactured in 24 gauge, though 22 gauge is often used.

People tend to classify SSRS as either structural or architectural, but those two distinctions aren’t absolute. There are many architectural SSRS that are structural systems, and most structural SSRS can be used in an architectural application. I think the better distinction is that SSRS are either water shedding or water barrier systems.

Water Shedding SSRSs

Water shedding panel systems are architectural SSRS, meaning they rely on gravity to shed water from the roof before it can build up on the metal panels. The steeper the roof slope, the faster the water will run off. However, in certain instances, these roofs still may allow water to infiltrate.

The following precautions can be taken to avoid this:

  1. Water shedding panel systems must be installed on a minimum roof pitch of 3:12 or greater. Panel manufacturers typically advertise the minimum recommended slope for each of their products.
  1. They must be installed over a solid deck, since they are not structural panels.
  1. The deck must be covered with a moisture barrier or membrane. This is critical as the moisture barrier is the last line of defense once water gets under the metal roof panels. The industry standard for years has been #30 felt. I think this should be considered the absolute minimum.

    A better, though more expensive solution is to use a peel and stick membrane. These are much more tear resistant and they will self-seal to nails and screws. Check with the membrane manufacturer about ventilation requirements as these membranes can trap moisture in the attic space if it is not well ventilated.

  1. Keep the design simple. Because these roofs only shed water, intricate trim details are usually not as watertight as those used with water barrier systems. Valleys, hips and other architectural effects can certainly be utilized, but with them comes a much greater chance for water intrusion.

Next post, I’ll get into the applications for water barrier standing seam roof systems

A standing seam metal roof system from MBCI is one of the most durable and weathertight roof systems available in the industry. So when your design requires a roofing system that is both aesthetically pleasing and structurally sound, choose one of MBCI’s six standing seam metal roof systems. Read more.

 

Choosing the Right Metal Roof System for the Job

It should be no surprise that I’m a strong advocate of the outstanding benefits of metal roofing. It is extremely, durable, low maintenance, energy efficient, recyclable –yes, I could go on and on. And it’s not just functional; it’s attractive. Its versatility is a designers dream when it comes to achieving today’s architectural elements—hips, valleys, slope changes, transitions and dormers are all possible.MBCI's 7.2 Panel

But as great as these roofs are, care must be taken to select the right type of metal roof system for the job at hand. In fact, the designer must specify a roof panel that can be used in each of the design elements he or she intends to incorporate into the roof project. Design, coupled with the choice of roof slopes, trim details and how the panel is to be fastened to the substructure are deciding factors in choosing the proper roof. When the roof system chosen isn’t the right one for the job, the result can be a roof that leaks and doesn’t function as designed.

Though most metal roofing manufacturers are able and willing to discuss the application parameters for each of their products, it would be wise to arm yourself with at least a general idea about the parameters of some of the most common profiles. To arm you as simply as possible, I’ll separate metal roofing into two broad categories—through fastened and standing seam.

Through-Fastened Roof Systems

Exposed, or through-fastened panels, are available in a variety of widths, usually from two to three feet wide. They also come in various rib shapes, heights and spacings. Typical gauges are 29 and 26, but they also come in 24 and 22 gauge.

There are structural and non-structural through-fastened panels. Structural panels are capable of spanning across purlins or other secondary framing members such as joists or beams. Non-structural panels must be installed over a solid deck.

Through-fastened roofs generally have two great advantages: (1) they are relatively inexpensive and (2) they are simple to install. Structural though-fastened panels have the additional advantage of providing a diaphragm, which is important in the wind bracing of metal buildings.

But most through-fastened roofs also have two big disadvantages: (1) they can leak if not fully seated to the panel or if the purlin is missed, and (2) they do not allow the roof to float during thermal movement. This can cause the roof panel to tear around the fasteners, causing leaks and possible roof blow off.

For this reason, through-fastened roofs are best suited to small- and medium-sized metal buildings and residential applications. In both instances, the panel runs are limited to shorter lengths where thermal movement is typically not a problem.

I’ll discuss the best uses for standing seal metal roofing systems in detail in my next two posts.

To support our customers’ design flexibility, MBCI offers 11 different metal roofing panels with exposed fasteners, each with its own unique profile. Most of these roof panels can also be used in wall applications and designed for both vertical and horizontal installation. Read more.

Details, Details, Details

Water runs downhill.  And, gravity is our friend.  Yet sometimes we forget these basic concepts when installing metal panel roofing.

When it comes to metal roofing details, a contractor should always think about the flow of water.

Roofing contractors are in the business of controlling water, so let’s install details that allow water to run downhill and let’s use gravity to our advantage.  A more precise way to say it: Implement drainage details that don’t buck water!

Details, details, details

Defending Against Water Leaks

Metal roof penetration and edge details should not rely on sealant as the primary defense against water leaks.  Certainly, sealant is and should be used as a secondary measure against water leaks.  Consider this: A transverse panel seam is created by lapping the upper panel over the lower panel, and sealant is used as a secondary seal.  Installers would never reverse the lap of a transverse seam (where the lower panel is on top of the upper panel), bucking water and relying only on sealant to keep water out.  A penetration detail (e.g., a vent stack or roof curb) should use the same logic.  There’s no doubt that bad details are rooted in low cost and speed of installation, but those are not details that are going to have equal service life to the metal panels on a roof.  A penetration detail is as critical to the long-term success of a metal roof as a transverse seam.

Prefabricated Penetration Details

It’s best to use prefabricated penetration details that have welded or soldered weathertight seams.  The prefabricated piece should be the width of a panel and include the male and female seams, and be seamed into the adjacent panels.  And just like a typical transverse seam, the top edge of the prefabricated piece should be under the upper panel, and the bottom edge of the prefabricated piece should be above the lower panel.  Water is not bucked and seams are fully intact.  That is a long-term penetration detail.

Where proper overlap can’t happen, redundancy is necessary.  A small pipe penetration detail should use a rubber roof jack with added levels of redundancy for weatherproofing.  First, the roof jack should only be installed in the flat of the panel; sealant tape should be installed between the panel and the roof jack; and closely spaced, gasketed fasteners should be installed to create compression on the sealant.

Roofing That Lasts

Metal roofs sell themselves because metal is long-lasting.  And construction details need to be developed and installed with that in mind.  Metal panels don’t leak—the joinery and fastener locations can leak.  Remember to design and build details that have equivalent service life to the panels themselves.  Proper laps are critical, and remember, gravity is our friend.

To learn how to design a roof system that prevents possible infiltration and allows for proper water runoff, take MBCI’s AIA-accredited course, The Devil is in the Details.

Code Requirements for Cool Roofs with Climate Zone Specifics

There is still a lot of discussion—some agreeable and some not so agreeable—about the necessary color of our rooftops.  One side of the discussion revolves around keeping the surfaces of our built environment “cool,” so there’s a movement to make all rooftops “cool” by making them white, or at least light-colored.  Those on the other side of the discussion claim that cool roofs are necessary to reduce a building’s energy use.  Cool roofs can be a really good idea, but let’s not mix up the reasons why cool roofs matter—are we cooling the urban areas (that is, reducing urban heat islands), or are we saving energy costs for individual buildings? Cool Roofs
h
The average building height in the United States is less than two stories, but “white roofs” are mostly desired in dense, urban areas…and how many buildings here are less than two stories?  Tall buildings are typically found in dense, urban areas, with shorter buildings dominating the fringe urban areas.  In the suburbs and rural areas, one- and two-story buildings are more the norm.  So we have a mix of building heights in the United States, but the conflict is that the “cool roof” focus is often where the tallest buildings exist.

And unfortunately, a cool roof on a 20-story building isn’t going to reduce its energy use, especially if the code-required amount of insulation exists on that roof.  Rather, reducing energy use of a 20-story building hinges on the energy efficiency of the 20-story-tall walls—R-value of walls, percentage of windows, and solar blocking eaves, just to name a few items.  Conversely, the energy efficiency of a one-story big-box store comes down to its roof.  And for these buildings, roof color definitely can make a difference.  However, our building codes don’t differentiate based on building proportions, but only on geographic location—and that’s problematic.  But as designers, we can improve on the code requirements.

The 2015 International Energy Conservation Code provides specific information about cool roofs, which are required to be installed in Climate Zones 1, 2, and 3 on low-slope roofs (<2:12) directly above cooled conditioned spaces.  There are two ways to prescriptively comply with this requirement: use roofs that have a 3-year-aged solar reflectance of 0.55 and a 3-year-aged emittance of 0.75.   Notice that initial (i.e., new) reflectance and emittance are not specified; long-term values are more important.  The second method to comply is to have a 3-year aged solar reflectance index (SRI) of 64.  SRI is a calculated value based on reflectivity and emittance.  It’s important to understand why a cool roof is desired and to make appropriate design decisions.

To locate metal roof products that meet the IECC requirements, go to http://coolroofs.org/products/results and use the search function to narrow your results or view our finishes’ SRI ratings on our Cool Metal Roofing page.

The Right Team Holds Your Standing Seam Roof System Together – Part 2

Blackridge Elementary features LokSeam
Blackridge Elementary features LokSeam

In my previous post, I talked about the important process of selecting the right materials and appurtenances for your standing seam roof system and how they should be used together for the best result.  There are three more parts of the standing seam roof system that, if used, must be carefully specified.

Pipe Penetrations.  Plumbing vents, heater flues, exhaust fans and pipe supports for equipment racks are all typical penetrations seen on metal roofs. Always specify rubber roof jacks for these penetrations, and use high temperature silicone rubber roof jacks on pipes that will be hot. Do not allow the use of residential type roof jacks, such as those made of plastic or lead, or the EPDM roof jacks made for single ply roofs.

Use pipe instead of square tubing to penetrate the roof when designing an equipment rack for rooftop equipment. Otherwise, there will be no good way to seal it to the roof. Pipe penetrations should always penetrate the roof in the middle, or flat part, of the panel, not through the seam itself. Ignore this advice, and you’ll probably have a roof leak on your hands.

Large diameter pipes may restrict the drainage of water. A good rule of thumb is to ensure that the base of the roof jack fits completely in the pan of the roof panel. If it will not fit, install a stack flashing in the roof at the proper location and attach the roof jack in the stack flashing. Stack flashings install into a roof just like a roof curb, but they are flat in the middle and don’t have the opening a curb does. This provides a large flat area in which to install the roof jack with room for water drainage.

Crickets. The roof design may at times require a cricket be installed to divert water around a parapet wall. And if the specifications or architectural drawings are not clear as to the proper treatment of this area, the roofer will make the cricket out of sheet metal.  However, crickets should always be made out of welded aluminum or stainless steel. This allows you to have a cricket that fits and leaves no pinholes or laps that are sealed with caulk. Sunlight will eventually break down exposed caulk and may cause a leak. But when properly built and installed, a welded cricket will perform throughout the lifetime of the roof.

Snow Retention Devices. When these devices are required on a standing seam roof, never use a through-fastened device. When through-fastened devices are used, they are either installed into the secondary structural, which prevents the roof from floating, or they are installed into the roof panels only, which makes for a very weak connection that will eventually work loose, leaving holes in the roof.

The best snow retention devices utilize a clamp that locks onto the panel seam and does not perforate the roof membrane.

Keep in mind that if snow conditions are severe enough to warrant retention devices at the eave, you will also need to protect pipe penetrations as well. Many unprotected plumbing vents are broken at the roof surface from moving ice and snow.

Remember, the roof system is called a system for a reason. For a successful roof installation, all rooftop accessories should be considered. Well defined specifications and details should be provided and adhered to so everyone involved in the project knows what is expected and can bid the project accordingly.

The roof installation process will be more efficient, leak problems will be avoided and the “final inspection” will be painless. Who doesn’t want that? The end result will be a total roof system that looks good and performs well for decades to come.

The Right Team Holds Your Standing Seam Roof System Together – Part 1

The architect, roof manufacturer and roof construction installer are parts of a team that can work together like a well-oiled machine to get the best result – a professionally installed roof that looks beautiful and will last for decades.

I now invite you to think of your metal roofing system as a “team” in the sense that all parts must work effectively and efficiently together like pieces of a puzzle to function optimally as designed. A well-thought-out process puts the right combination of materials together in the right way to produce an optimum roofing system.

The process requires identifying a reputable manufacturer of standing seam roofs – one that meets your specific performance and aesthetic needs, and that provides the required warranties. Once chosen, the designer may think, “Voila! Mission complete,” when in fact, the process is just beginning.

BattenLok and LokSeam
Mitchelle Elementary School features BattenLok HS and LokSeam

 

 

Since metal roofs are being used in increasingly more complicated designs, the roof panels and related accessories that attach the roof to the substructure are a part of the total roof system. The added roof curbs, pipe penetrations, crickets, snow retention devices and lightning protection equipment all become part of the standing seam roof system.  And it really matters how each of these items attach to the roof.  Though it sounds logical to do so, don’t leave it up to the roofer or another tradesperson to decide how these items will be installed.

Take control and make sure the following are adhered to when specifying a standing seam metal roof system:

Do not use dissimilar materials.

 Copper, lead and graphite can all cause galvanic corrosion. Even water dripping from these materials onto the roof can cause it to corrode. And manufacturers’ warranties are often void if this situation exists.

Some examples: Copper lightning arresting equipment is a typical use of dissimilar material found on Galvalume roots. Use aluminum instead. Lead hats are often found on Galvalume roots. Rubber jacks can be substituted.

Compile a qualified list of acceptable curb manufacturers. Choose only those that use aluminum or stainless steel. Many curb companies use Galvalume, which seems reasonable since most standing seam panels are made from this material. But when Galvalume-coated steel is welded, the Galvalume-coating melts at the weld. Even when a coating of corrosion inhibitor is used, it will never be as good as the uncontaminated Galvalume coating.

You also want a curb manufacturer that offers a weathertightness warranty if required for the roof. Roof manufacturers will generally warrant the attachment of the roof curb to their roof panels, but it’s up to the roof curb manufacturer to warrant the construction and performance of their product.

Be careful with roof curbs.  First off, they should be “shingled” into the roof. This way, all laps shed water as it drains from the roof. Curbs that lap on top of the roof panels on the upslope side will cause problems.

Roof curbs must allow plenty of room for water to drain around them without building up a waterhead at the upslope end.  Provide clearance on both sides of the curb and a long flange on the upslope end so the roof panels can lap onto the flange and maintain a 12” upslope from the top of the water diverter built into the curb.

Finally, if AC units will be placed on the roof, include PVC condensate lines to carry the water off of the roof. Never allow the condensate to drain directly onto the roof. The dissolved copper ions which will cause galvanic corrosion of the roof panels.

This is a lot to consider, possibly more than you thought was involved. Well friends, there’s even more. I’ll explore this even further in my next post.

In the meantime, learn more about MBCI’s rigorously-tested, standing seam metal roof systems and how it’s one of the most durable and weathertight roof systems available in the industry.

Find a sales representative